Apollo XP95 55000-400APO Addressable Standard Temperature Heat Detector
AED 180.00
Get a Free Quote Enquire via WhatsAppThe Apollo XP95 55000-400APO is an addressable standard-temperature static heat detector (Class A2S) featuring a fixed 55°C alarm threshold, XPERT card base addressing, polarity-insensitive 2-wire connection, and 360-degree LED indication.
Did you like this product? Add to favorites now and follow the product.
Description
The Apollo 55000-400APO is an open-area analogue-addressable standard-temperature thermal heat detector designed for commercial, industrial, and institutional fire protection systems. Utilizing a single NTC thermistor network housed in a low-airflow-resistance casing, the detector continuously monitors ambient temperature changes and produces an analogue voltage signal proportional to environmental heat. Classified as a Class A2S device under EN 54-5, it triggers an analogue alarm signal at a static threshold of 55°C, making it an ideal detection solution for environments where dust, steam, or smoke prevent the use of optical smoke sensors. The unit operates over a 17V to 28V DC loop supply, employs XPERT card mechanical addressing via the mounting base, includes a clear red status LED, and supports remote indicator connection.
Features
- Standard Thermal Static Sensing: Class A2S rated to report an alarm at 55°C, making it optimal for standard temperature environments requiring fixed thermal triggering.
- Single Thermistor Network: Monitors ambient air temperature using an internal NTC thermistor that returns an analogue signal directly proportional to external thermal changes.
- Passive XPERT Card Addressing: Address setting is held inside a passive address card stored in the base, eliminating internal switches or electronic programming tools.
- High Environmental Tolerance: Low airflow casing design renders thermal sensing completely unaffected by ambient wind velocity or atmospheric pressure changes.
- Dirty and Smoky Environment Suitability: Designed for locations where optical or ionization smoke detectors cause false alarms, such as commercial kitchens, boiler rooms, car parks, and dusty warehouses.
Specifications
- rand Name: Apollo Fire Detectors
- Model: XP95 55000-400APO
- Type: Analogue Addressable Standard Temperature Heat Detector (Class A2S)
- Operating Voltage: 17V to 28V DC
- Quiescent Current: 250 µA average / 500 µA peak
- Alarm Current: 2 mA (LED active)
- Static Response Temperature / Alarm Threshold: 55°C (Static)
- Operating Temperature Range: -20°C to +70°C
- Operating Humidity: 0% to 95% RH (Non-condensing)
- IP Rating: IP53 / IP54
- Dimensions: 100 mm (D) x 42 mm (H) (Detector head) / 100 mm (D) x 50 mm (H) (With base)
- Weight: 105 g (Detector head) / 157 g (With base)
- Housing Material: White polycarbonate V-0 rated to UL 94
- Addressing Method: XPERT card addressing via mounting base
- Compatible Base: Apollo XP95 / Discovery Base Series (Part No. 45681-210APO)
- Certifications: EN 54-5 (Class A2S), LPCB Approved, CPR Certified, VdS Certified, CE Marked