Description

The Honeywell Morley MI-DCZRM Zone Monitor Module allows a zone of conventional fire detectors to interface directly with an addressable fire alarm system. Designed to bridge traditional and intelligent detection, it powers and continuously supervises a zone of up to 30 conventional smoke or heat detectors using an end-of-line monitoring device. The module features built-in short-circuit isolation to preserve loop communication during wiring faults, tri-color LED indicators for clear visual diagnostic and alarm status, and simple rotary decade switches for fast manual addressing. Compatible with Morley-IAS protocol control panels, it comes housed in a durable backbox enclosure for straightforward field installation.

Features

  • Connects up to 30 conventional fire detectors directly to an addressable loop
  • Built-in short-circuit isolator maintains loop reliability during cable faults
  • Rotary decade switches enable quick and error-free device addressing
  • Tri-color LED status indicator displays normal, fault, and alarm conditions
  • External power supply monitoring ensures uninterrupted conventional zone power
  • Seamlessly compatible with Morley-IAS intelligent fire alarm control panels

Specifications

  • Brand Name: Honeywell Morley
  • Model Number: MI-DCZRM
  • Operating Voltage: 15VDC to 30VDC
  • External Power Supply: 18VDC to 30VDC
  • Standby Current: 300µA (at 24VDC, no communication)
  • Max Conventional Zone Current: 60mA
  • End-of-Line Resistor: 3.9k ohm or 4.7k ohm (configuration dependent)
  • Operating Temperature: -20°C to +60°C
  • IP Rating: IP30 (standard enclosure)
  • Dimensions (H x W x D): 93mm x 94mm x 23mm