Notifier RP-2001 | 6-Zone Conventional Releasing Control Panel

In Stock
Delivery within two days all over UAE.

AED 5,500.00

Get a Free Quote Enquire via WhatsApp

The Notifier RP-2001 is a UL-listed, six-zone conventional fire alarm control panel designed for high-performance management of single and dual-hazard deluge and preaction water-based suppression systems.

In Stock
Add to Wishlist
Add to Wishlist

Did you like this product? Add to favorites now and follow the product.

Add to Wishlist
Add to Wishlist
Have a Question? Ask a Specialist

+971 54 581 5314

Free Delivery

Above AED 1000

Warranty

For 365 days

Always Authentic

Only Reputed Brands

Easy Payments

Multiple payment options

Description

Description
The Notifier RP-2001 is a microprocessor-controlled fire alarm control panel (FACP) specifically engineered for buildings requiring water-based releasing systems. It is compliant with NFPA 13, 15, and 16 standards, offering reliable fire detection and signaling for commercial and industrial facilities. The panel supports the advanced System Sensor i3 detector series and is capable of sophisticated releasing logic, including cross-zoning and double-interlock. With its 80-character backlit LCD, it provides detailed real-time information for fire safety technicians and emergency responders.

Key Features
Specialized Releasing Logic: Designed specifically for deluge and pre-action sprinkler standards (NFPA 13, 15, and 16).
Cross-Zoning Capability: Supports double-interlock logic to prevent accidental discharge in high-sensitivity environments
System Sensor i3 Compatible: Enables the panel to receive “clean me” maintenance signals and freeze warnings from i3 detectors.
Customizable Timers: Features adjustable waterflow discharge timers and dual soak timers for precise suppression control.
Intuitive Interface: Integral 80-character backlit LCD display with a real-time clock and automatic daylight savings adjustment.
Robust Power Supply: Integrated 7.0 Amp power supply with 24V DC special application power for resettable devices.
Extensive History Log: Non-volatile memory stores up to 256 system events for audit and diagnostic purposes.
Silent Walk Test: Allows technicians to test the system without activating audible alarms or releasing solenoids.

Technical Features
Manufacturer: Notifier by Honeywell
Model: RP-2001 (120V) / RP-2001E (240V)
Initiating Zones: 6 Class B (Style B)
Output Circuits: 4 Class B (Style Y); Rated at 3.0 Amps each
Input Power (RP-2001E): 240V AC, 50/60 Hz, 2.085 Amps
Total System Power: 7.0 Amps @ 24V DC
End-of-Line Resistor (EOL): 4.7K Ohms, 1/2 Watt (IDCs and NACs)
Battery Charger Capacity: Up to 26 Ah (Internal cabinet fits up to 18 Ah)
Relay Contact Rating: 2.0 Amps @ 30V DC
Enclosure Rating: IP30 / NEMA 1 equivalent
Operating Temperature: 0°C to 49°C (32°F to 120°F)
Dimensions (H x W x D): 48.26cm x 42.29cm x 13.34cm (19.0″ x 16.65″ x 5.25″)
Certifications: UL Listed (S635), FM Approved, CSFM, MEA

 