Potter PAD200-PHD Photoelectric Smoke/Heat Detector Combination
The Potter PAD200-PHD is an advanced, addressable multi-criteria detector combining optical photoelectric smoke sensing with electronic thermistor heat detection in a single low-profile housing. Operating on the Potter Addressable Device (PAD) loop protocol, this combination detector provides software-selectable thresholds for both smoke obscuration and heat tracking while meeting strict UL 268 7th Edition guidelines.
Did you like this product? Add to favorites now and follow the product.
Description
The Potter PAD200-PHD combination multi-sensor offers intelligent fire protection for spaces requiring highly reliable smoke and thermal monitoring, such as modern multi-family complexes, educational facilities, and commercial office networks. By running simultaneous analysis on both its internal optical chamber and integrated thermal circuit, the device evaluates real-time environment metrics to verify smoke particles and rapid temperature changes before alarming. This dual-criteria processing ensures faster detection of volatile synthetic fires while dropping nuisance alarms from typical indoor triggers like steam and dust. It transfers data continuously over standard 2-wire Signaling Line Circuits (SLC) using the analog PAD protocol. Hardware addresses are assigned locally via rugged 7-position DIP switches mounted directly to the plastic frame, bypassing the need for electronic programming accessories. The detector head fits with a twist-lock motion into any PAD100 series mounting layout, featuring clear status LEDs for easy visual validation from floor level.
Features
- Dual-Signature Multi-Criteria Sensing: Houses an advanced optical smoke chamber and an accurate electronic thermistor together to recognize diverse structural fire risks quickly.
- UL 268 7th Edition Compliance: Fully certified under modern life safety standards to reduce nuisance alarms from common kitchen aerosols while optimizing responses to real fire conditions.
- Onboard Drift Compensation: Proactively tracking dust and soil buildup within the photoelectric optical cell, adjusting calibration algorithms automatically to keep performance stable.
- Hardware-Based Addressing: Eliminates the need for specialized external handheld software programmers by using simple, reliable binary DIP switches on the rear of the device head.
- Continuous Panel Supervision: Interrogates continuously over the proprietary PAD SLC digital path, completing a total device communication loop verification in under 5 seconds.
- Cross-Base Mechanical Fit: Locks cleanly into existing PAD series infrastructure bases, including standard 4-inch (PAD100-4DB) or 6-inch (PAD100-6DB) setups, as well as specialized isolator, relay, or sounder accessories.
Specifications
- Brand Name: Potter Electric Signal Company, LLC
- Part Name: Photoelectric Smoke / Heat Detector Combination
- Model Number: PAD200-PHD
- Operating Voltage: 24 VDC
- Detector Current Draw: 300 µA (Standby)
- Alarm Set-Point Range (Smoke): 1.0% to 3.5% per foot obscuration
- Alarm Set-Point Range (Heat): 135°F (57°C) Fixed Temperature
- Rate-of-Rise Detection: 15°F/min (8.3°C/min) — Selectable Option
- Addressing Method: Onboard Rear DIP switches (Addresses 1 to 127)
- Alarm Indicator: 1 Multi-status LED (polling and active alarm flash)
- Air Velocity Rating: 0 to 300 feet per minute (Open Area Protection)
- Installation Temperature Range: 32°F to 120°F (0°C to 49°C)
- Operating Humidity Range: 0% to 93% RH (Non-condensing)
- Dimensions (Without Base): Height: 1.94 in (49 mm) | Diameter: 3.93 in (100 mm)
- Weight (Without Base): 102 g (3.6 oz)
- Certifications: UL 268 7th Edition Listed, UUKL Listed for Smoke Control